Fire Fighting Pump Control

High-reliability diesel engine, jockey pump, and main pump automation and control solutions.

Premium Protection

Fire Fighting
Pump Control Solutions

Teknocrat’s fire fighting pump control solutions includes diesel engine , jocky pump & main pump control systems.

Safety Compliant

Built to meet stringent national and international fire safety standards.

Automation Control

Multi-stage auto start sequences and status tracking.

Fire Fighting Pump Control Panel
Fire Fighting System Control

System Specifications Comparison

Review specifications for Jockey/Main pumps versus Diesel engine driven systems.

Feature / ParameterJocky or main Pump control systemControl system for diesel engine driven pump
DescriptionPump starter systems suitable for fire fighting pumpAutomation control system suitable for automated operation of diesel engine driven pumps used in fire fighting system
Available ratings1 to 250 HP ( DOL / SD )Not applicable
Input supply Voltage415 VAC, 3 phase230VAC , 1 phase
Control voltage230VAC12VDC / 24 V DC , Negative Earth
ProtectionsShort Circuit / Overload / Phase failureEngine Start Failure, Low Lube Oil Pressure, High Water temperature, Engine overspeed, Low fuel level
Audio / visual IndicationNAEngine Start Failure, Low Lube Oil Pressure, High Water temperature, Engine overspeed, Low fuel level
Visual IndicationPump run / tripEngine Run, Hooter Off, Hydrant pressure normal, AC supply On.
FeaturesAuto start operation based on external pressure switch, Optional manual start facility3 nos. of automated start attempts with 15 sec. interval time . Auto / Manual mode, Trickle/ boost charging of batteries